SILCOR IAS Rigid light type conduit
- CLASS:23411
- IMPACT RESISTANCE:2J
- RESISTANCE TO COMPRESSION:320 Nt
SILCOR rigid conduit has been produced since 1992 and is a part of SILCOR – SIFLEX conduit system for cable management and protection. It’s ideal for concealed installations and exposed installations with light mechanical requirements. SILCOR achieves high impact compression (2J) in low temperature environments (-25οC), ensuring safety in the electrical installation. It’s assembled with CONDUR fittings (couplers, clips, adaptors) and junction boxes.
APPLICATION FIELD
Ideal for indoor exposed installations with light mechanical requirements such as commercial buildings, residential buildings. Their high impact strength, at low temperature environments,make them also ideal for cold weather conditions.
- APPLICATION STANDARD:EN 61386.21
- INSTRUCTIONS FOR COMPLIANCE:2014/35/EU(LVD), 2011/65/EU(RoHS)
- COLOR:RAL 7035 Light grey
- NOMINAL DIAMETER:Nominal outer diameter (DN/OD)
- TIGHTNESS DEGREES:min IP 65
- Product Conformity to all requirements of relative European Directives.
- The product and its production process are inspected and approved by VDE German institute
- Minimum resistance to compression
- Minimum resistance to impact
- Min-max permanent application temperature
- Ingrees protection against solid objects and water (EN 60529)
- Non flame propagating product
- Antistatic Technology IAS (Patent Protected 1009870)
- PROPERTIES
- CHARACTERISTICS
- PACKAGING
- RECOMMENDED APPLICATIONS
- DOWNLOADS
- PROJECTS
Properties | Class | |
Resistance to compression | 320Nt/5cm | 2 |
Resistance to impact | 2J (at -25oC) | 3 |
Lower temperature range | -25oC | 4 |
Upper temperature range | +60oC | 1 |
Resistance to bending | Rigid | 1 |
Electrical characteristics | With electrical insulated characteristics | 2 |
Protection against ingress of solid objects | min IP65 | 6 |
Protection against ingress of water | min IP65 | 5 |
Resistance against corrosion | Not applicable | 0 |
Tensile strength | None declared | 0 |
Resistance to flame propagating | Non flame propagating | 1 |
Suspended load capacity | None declared | 0 |
Fire effects | None declared | 0 |
Environmental impact | None declared | 0 |
Additional properties | ||
Raw material | Heavy metals free (RoHS), specially stabilized thermoplastic U-PVC | |
Antistatic technology | Protection against static electricity |
Type | Part number | |||||
Ø16 | 1003016 | 16 | 13.8 | 90 | 5,42 | 7920 |
Ø20 | 1003020 | 20 | 17.7 | 60 | 5,09 | 5400 |
Ø25 | 1003025 | 25 | 22.5 | 45 | 5,23 | 3240 |
Ø32 | 1003032 | 32 | 29.4 | 30 | 4,87 | 1890 |
- Recommended
- Not recommended
- Ideal according to the manufacturer
SCOPES | |
Exposed | |
Concealed (underplaster) | |
Concealed (dry wall) | |
Concrete | |
Underfloor in screed | |
Outdoor | |
Buried Wood (underground) | |
Wood | |
Concealed floor / ceiling |